M-Bus

Kconfig: CONFIG_MODULE_MBUS — GClasses: C_PROT_MBUS_M

M-Bus (Meter-Bus, EN 13757) master: reads the water, heat, gas and electricity meters of a wired M-Bus. The module has two parts:

Source code:

The bus, in short

M-Bus is a two-wire bus, with no polarity, that also powers the meters. The master talks by moving the bus voltage, and a meter answers by moving the current it draws. So a serial port alone cannot drive it: the master needs an M-Bus level converter, on USB or RS-232, or a transparent M-Bus to TCP gateway that passes the bytes as they come. For this gclass both are a stream of bytes: a C_UART in the first case, a C_TCP in the second.

The bus runs at 2400 baud, 8E1 (8 bits, even parity, 1 stop bit) unless it is set up otherwise. A long frame is up to 261 bytes, about 1.2 s on the wire, so a cycle of 250 meters takes minutes. That is fine for meters of water and gas.

A meter describes its own data. It answers with a list of records, and each record carries its quantity, its unit and its scale. So one decoder serves every manufacturer, and there is no register map to write, as there is in Modbus.

C_PROT_MBUS_M

register_c_prot_mbus_m()

Registers the gclass. A yuno that reads a bus calls it with the rest of its gclasses:

int register_c_prot_mbus_m(void);
static int register_yuno_and_more(void)
{
    int result = 0;
    result += register_c_prot_mbus_m();
    result += register_c_my_gate();
    return result;  // a gclass refused stops the yuno
}

The master is a child gclass: it publishes to its parent (or to its subscriber), so the parent declares EV_ON_OPEN, EV_ON_MESSAGE and EV_ON_CLOSE in its FSM.

hgobj gobj_mbus = gobj_create("bus1", C_PROT_MBUS_M,
    json_pack("{s:s, s:[{s:i}, {s:s}]}",
        "url", "/dev/ttyUSB0",
        "slaves",
            "address", 1,
            "secondary", "12345678"
    ),
    gobj
);
gobj_start(gobj_mbus);

Configuration

The bottom is made from url when the parent gives none: a C_TCP for tcp://host:port, else a C_UART with baudrate, bytesize, parity and stopbits. slaves lists the meters to read: one by its primary address (1-250), or one by its secondary address, the 8 digits of its identification. A secondary address can also give the manufacturer (3 letters), the version and the medium (a name or a code), so that two manufacturers with the same number are not taken for one meter.

{
    "url": "/dev/ttyUSB0",
    "baudrate": 2400,
    "parity": "even",
    "timeout_polling": 60000,
    "timeout_response": 500,
    "retries": 2,
    "max_telegrams": 8,
    "slaves": [
        {"address": 1},
        {"address": 2, "disabled": true},
        {"secondary": "12345678"},
        {"secondary": "87654321", "manufacturer": "KAM", "medium": "water"}
    ]
}

The same bus behind a gateway:

{
    "url": "tcp://192.168.50.20:10001",
    "slaves": [{"address": 1}, {"address": 7}]
}
AttributeDefaultMeaning
urlSerial device of the level converter, or tcp://host:port of a gateway
baudrate, bytesize, parity, stopbits2400, 8, even, 1Serial line, given to the C_UART. They also bound how long an answer may last (the wire time of two frames), read from the C_UART when each request goes (the bottom of the master, or a C_UART under other layers below it: the first gobj of the bottom chain that has a baudrate): what the line runs at, so a speed its tty does not know counts at 9600, the speed it runs at (up to 7.29.3 the master counted with its own attrs, once, at create). A baudrate of 0 or less is an error, and 2400 is taken and given to the C_UART. Behind a tcp:// gateway, set them to the speed of the gateway’s bus: there the master’s own attrs count
slaves[]The meters. They are read at start, so a change needs a stop and a start
timeout_polling60000Milliseconds from the end of one cycle to the start of the next
timeout_response500Milliseconds of silence allowed: from the request to the first byte of the answer, and from each chunk of bytes to the next. EN 13757-2 gives a meter about 190 ms at 2400 baud to start. The rest is margin for a gateway. It is not the time of the whole answer: a long frame is about 1.2 s on the wire
retries2Times a request without a valid answer is sent again
max_telegrams8The most telegrams in one reading

A slave that is not written correctly is left out, with an error: a primary address outside 1-250 or repeated, a secondary that is not 8 digits (an F is a wildcard digit), a medium the decoder does not know, or both an address and a secondary.

The cycle

The slaves are read one after the other:

primary:     SND_NKE -> E5,  REQ_UD2 -> RSP_UD  [REQ_UD2 -> RSP_UD ...]
secondary:   SND_UD select (CI 52) -> E5,  REQ_UD2 to FD -> RSP_UD  [...]

The master publishes EV_ON_OPEN when the transport connects, and starts a cycle at once. On EV_DISCONNECTED it drops the reading in progress and publishes EV_ON_CLOSE. The transport reconnects on its own, and a new cycle starts then.

What a reading carries

It publishes one EV_ON_MESSAGE per slave read, as soon as its reading is complete. It does not wait for the end of the cycle, because a cycle can be minutes long and the reading has to carry the time it was read.

{
    "address": 1,
    "header": {
        "id": "06855817", "manufacturer": "KAM", "version": 8,
        "medium": "heat", "medium_code": 4, "access_no": 4, "status": 0
    },
    "records": {
        "energy":           {"value": 37351000, "unit": "Wh"},
        "volume":           {"value": 561.08, "unit": "m3"},
        "volume@s1":        {"value": 500.98, "unit": "m3"},
        "flow_temperature": {"value": 101.69, "unit": "C"},
        "datetime":         {"value": "2011-01-05T15:26"}
    },
    "telegrams": 1
}

A slave read by its secondary address carries "secondary": "12345678" in place of address. header, the id of each record and the units are those of mbus_decode_user_data(). A reading in several telegrams has the records of all of them, and a record whose id repeats an earlier one takes the next #n.

Only what was read. A slave that was not read in a cycle publishes nothing in that cycle. Its earlier reading is never sent again, and a meter that does not answer never comes out as zeros.

Failures

A slave whose read fails is logged as a warning (msgset Protocol): “M-Bus slave not read”, with the slave and the reason. It is logged when the slave starts failing, or starts failing in another way, not on every cycle. When the slave is read again, an info says so, with what it had failed with:

{"msg": "M-Bus slave not read", "slave": "2", "reason": "no answer to SND_NKE",
 "detail": "", "bytes": ""}
{"msg": "M-Bus slave answered again", "slave": "2",
 "failed_with": "no answer to SND_NKE"}
reasonWhen
no answer to SND_NKE / to the selection / to REQ_UD2The step had no answer, with all its retries
bad frame to ...The last attempt got bytes that are not a frame (detail says why, bytes shows the first 64)
bad answerA valid frame, but not the one asked for: no E5, an RSP_UD of another slave, or no records
undecodableAn RSP_UD the decoder refuses: fixed data (CI 73), records encrypted, a record cut short
application errorThe meter answered CI 70

Bytes that arrive with no request in flight are dropped, with one warning (“M-Bus bytes with no request in flight, dropped”) until the next valid answer.

Stats

StatCounts
txFramesFrames sent
rxFramesValid frames received
badFramesFrames that do not parse, or are not the answer asked for
timeoutsRequests with no answer: timeout_response of silence and no byte of a bad frame
repeatsRequests sent again
readingsReadings published
failedReadsReads of a slave that failed

They are the communication diagnostics a meter network is asked for (frames sent and received, bad frames, retries), and they are read like any other stat:

ycommand -c 'command-yuno id=<yuno> service=<gate> command=stats'

Commands

dump-data gives the last reading of each slave, whether it is disabled, and what it is failing with ("" when it is read). It takes address or secondary to give one slave only. A slave that does not exist answers -1 (“M-Bus slave not found”).

json_t *resp = gobj_command(gobj_mbus, "dump-data",
    json_pack("{s:i}", "address", 1),
    gobj
);

read-now starts a cycle at once, without waiting for timeout_polling. It answers -1 when the bus is not between cycles (not connected, a cycle or an operation in progress).

ycommand -c 'command-yuno id=<yuno> service=<gate> command=read-now'

Operations: putting meters into service

Three commands work on the bus itself. A command checks its arguments, starts its operation and answers at once. The operation runs when the bus is free: at once between cycles, or at the end of the cycle in progress. The cycle waits while it runs, and goes on timeout_polling after it. Only one runs at a time; a second one answers -1. operation-status gives the state (waiting, running, done, failed) and the result. The end is logged: “M-Bus operation done” as an INFO, with the number found, or “M-Bus operation failed” as a WARNING, with the reason. A bus that closes fails the operation in progress.

ycommand -c 'command-yuno id=<yuno> service=<gate> command=scan-secondary'
ycommand -c 'command-yuno id=<yuno> service=<gate> command=operation-status'
{
    "operation": "scan-primary",
    "state": "done",
    "args": {"from": 1, "to": 5},
    "asked": 1792750000,
    "ended": 1792750003,
    "error": "",
    "found": [
        {"address": 1, "secondary": "11111111", "manufacturer": "KAM",
         "version": 1, "medium": "water", "medium_code": 7},
        {"address": 4, "collision": true}
    ]
}

An entry of scan-secondary has the secondary and the primary address the meter answered with (0 when it has none). An entry that could not be told apart carries "collision": true, and one that answered the probe but not the REQ_UD2 carries an error.

Trace levels: messages (each reading published), traffic (raw bytes, both ways), polling (each step of the cycle and of the operations, what each scan finds, and a slave with more telegrams than max_telegrams).

What it does not do (yet)